Not all menu items display on standard meters.

MENU CONFIGURATION
(Defaults in Bold and Italics)

MENU
/DEV
/MAX
INPT
INPUT TYPE
Show input choices:
Input Type J.TC Iron vs. Constantan (NIST)
K.TC Chromel vs. Alumel (NIST)
DJ.TC Iron vs. Copper (DIN)
T.TC Copper vs. Copper-Nickel
DEC.P
Decimal Point
Show decimal point position
FFFF.
FFF.F
RD.CF
Reading Configuration
R.1
C: Celsius
F: Fahrenheit
S1.CF
SETPOINT 1 CONFIGURATION
S.1


S.2
A: Active above
B: Active below

U: Unlatched
L: Latched
S2.CF
SETPOINT 2 CONFIGURATION
S.1


S.2
A: Active above
B: Active below

U: Unlatched
L: Latched
S1.DB
SETPOINT 1 DEADBAND
Scroll right one digit
Change flashing digit's value
S2.DB
SETPOINT 2 DEADBAND
Scroll right one digit
Change flashing digit's value
Output Configuration Analog Output
0.1


0.2


0.3


0.4




0.5
D: Disabled
E: Enabled

V: Voltage analog out
C: Current analog out

A: Retransmission of temperature
P: Proportional to error

D: Proportional analog output is direct reading
R: Proportional analog output is reverse acting

F: 0-10 V proportional
H: 0-5 V proportional
Notes
*
If you select 0.2=V, you may select your analog output to be 0-10 V or 0-5V by accessing sub-menu 0.5=F or 0.5=H
* If 0.3=P, you may select your proportional output analog to be direct 0.4=D (4-20 mA), (0-5V), (0-10v) or reverse acting 0.4=R (20-4 mA), (5V-0V), (10V-0V).
P.BND
Proportional Band
Show prior value entered
Change flashing digit's value
M.RST
Manual Reset
Show prior value entered
Change flashing digit's value
OT.S.O
Output Scale/Offset

Enter new value & show "OUT1"


Enter new value & show "RD 2"


Enter new value & show "OUT2"
Show "RD 1" & prior value

Scroll right one digit

Show prior value

Scroll right one digit

Show prior value

Scroll right one digit

Show prior value
Change flashing digit's value


Change flashing digit's value



Change flashing digit's value



Change flashing digit's value
C.J.OF
Cold Junction Offset
Show actual or prior value
Change flashing digit's value (░C only)
LK.CF
Lock Out Configuration
RS=


SP=


L3=
E (Enable RESET button in run mode)
D (Disable RESET button in run mode)

E (Enable setpoint changes)
D (Disable setpoint changes)

0 (SETPTS button display setpoint values)
1 (SETPTS button display software "v.-03" version)